- 8 KVA :
Output
Output power capacity
8.0 KWatts / 8.0 kVA
Max Configurable Power (Watts)
8.0 KWatts / 8.0 kVA
Nominal Output Voltage
230V
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Other Output Voltages
220, 240
Load Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform type
Sine wave
Output Connections
(1) Hard Wire 3-wire (H N + G) (Battery Backup)
(4) IEC 320 C19 (Battery Backup)
(3) IEC Jumpers (Battery Backup)
(6) IEC 320 C13 (Battery Backup)
Bypass
Internal Bypass (Automatic and Manual)
- Input
Nominal Input Voltage
230V, 400V 3PH
Input frequency
40 - 70 Hz (auto sensing)
Input Connections
Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations
160 - 275V
Input voltage adjustable range for mains operation
100 - 275 (half load), 173 - 476 (half load)V
Other Input Voltages
220, 240, 380, 415
- Batteries & Runtime
Battery type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time
1.5hour(s)
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
Replacement Battery
APCRBC140
Expected Battery Life (years)
3 - 5
RBC Quantity
2
Extendable Run Time
1
- 10 KVA :
Output
Output power capacity
10.0 KWatts / 10.0 kVA
Max Configurable Power (Watts)
10.0 KWatts / 10.0 kVA
Nominal Output Voltage
230V
Output Voltage Distortion
Less than 2%
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Other Output Voltages
220, 240
Load Crest Factor
3 : 1
Topology
Double Conversion Online
Waveform type
Sine wave
Output Connections
(6) IEC 320 C13 (Battery Backup)
(4) IEC 320 C19 (Battery Backup)
(1) Hard Wire 3-wire (H N + G) (Battery Backup)
(3) IEC Jumpers (Battery Backup)
Bypass
Internal Bypass (Automatic and Manual)
- Input
Nominal Input Voltage
230V, 400V 3PH
Input frequency
40 - 70 Hz (auto sensing)
Input Connections
Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations
160 - 275V
Input voltage adjustable range for mains operation
100 - 275 (half load), 173 - 476 (half load)V
Other Input Voltages
220, 240, 380, 415
- Batteries & Runtime
Battery type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time
1.5hour(s)
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
Replacement Battery
APCRBC140
Expected Battery Life (years)
3 - 5
RBC Quantity
2
Extendable Run Time
1